Differential Pressure Valve
Flow-limiting dynamic balancing valve · TEB-25
The dynamic balancing differential pressure control valve balances the building's heating system so every floor receives the same heat. It needs no power, prevents noise caused by high flow and pressure, and avoids unnecessary bypass so pumps work less. Combined with thermostatic radiator valves, savings no longer depend on user habits.

Features
A proportional valve that compensates pressure differences between floors.
- Proportional control that needs no auxiliary energy.
- Hydronically balances the building's heating installation.
- Smooth, even heat distribution.
- Guarantees the flow required in the heating circuit.
- Prevents noise caused by high flow and pressure.
- Avoids unnecessary bypass so pumps run less.
- Factory setting 10 kPa.
- Fits horizontally or vertically on the return line.
- Setting range 5–25 kPa; 1 kPa per turn, 20 turns in total.
- Precise control in buildings with thermostatic radiator valves.
- Automatic savings independent of user habits.
- Can be re-adjusted in existing systems.
Technical data
The dimension and flow tables are for the DN20 body; please ask us for TEB-25 (DN25) values. Values may vary with installation and setting.
| Parameter | Unit | Value |
|---|---|---|
| Nominal size | – | DN20 |
| Kvs | m³/h | 1.2 / 1.6 |
| Pressure rating | – | PN25 |
| Max. differential pressure in system | bar | 4.5 |
| Medium | – | Water |
| Temperature range | °C | 4 – 100 |
| Connections | – | Female / male thread |
| Valve body and actuator | – | MS58 |
| Diaphragm | – | EPDM |
| Impulse tube | – | G 1/8", copper, Ø 3 mm |
| Dimensions (mm) | DN | L | H | D | Thread |
|---|---|---|---|---|---|
| Balancing valve | 20 | 73 | 108 | 60 | G1" |
| Limiting valve | 20 | 73 | 45 | – | G1" |
| Turns | Setting (kPa) | Min. flow (l/h) | Max. flow (l/h) |
|---|---|---|---|
| 0 | 5 | 28 | 560 |
| 1 | 6 | 31 | 610 |
| 2 | 7 | 33 | 660 |
| 3 | 8 | 35 | 710 |
| 4 | 9 | 38 | 750 |
| 5 | 10 (factory) | 40 | 790 |
| 6 | 11 | 42 | 830 |
| 7 | 12 | 43 | 870 |
| 8 | 13 | 45 | 900 |
| 9 | 14 | 48 | 935 |
| 10 | 15 | 48 | 970 |
| 11 | 16 | 50 | 1,000 |
| 12 | 17 | 52 | 1,030 |
| 13 | 18 | 53 | 1,060 |
| 14 | 19 | 54 | 1,090 |
| 15 | 20 | 56 | 1,120 |
| 16 | 21 | 57 | 1,150 |
| 17 | 22 | 58 | 1,170 |
| 18 | 23 | 60 | 1,200 |
| 19 | 24 | 62 | 1,250 |
| 20 | 25 | 63 | 1,290 |
Price and quote
The price of the differential pressure valve depends on the model, the quantity and the scope of installation. We therefore do not publish prices; we send a device list and a price offer for your project by e-mail.
Design and measurement architecture follow European standards.
Manufactured in our own facilities, with fast delivery and service.
When everyone pays for what they use, the whole building uses less.
Every device is tested before shipping, with spare parts for many years.
Let's choose the right devices for your building
Site surveys are free. Just tell us the number of flats and the type of installation.